Simple mode parameter list
Basic settings
5 - 8
쑶
I001747E
Fig. 5-6:
Setting the maximum frequency
NOTES
The output frequency is clamped by the Pr. 2 setting even the set frequency is lower than the Pr. 2
setting (The frequency will not decrease to the Pr. 2 setting.) Note that Pr. 15 "Jog frequency" has
higher priority than the minimum frequency.
When the Pr. 1 setting is changed, frequency higher than the Pr. 1 setting can not be set by the dig-
ital dial.
When performing a high speed operation at 120 Hz or more, setting of Pr. 18 "High speed
maximum frequency" is necessary. (Refer to section. 6.4.1.)
E
CAUTION:
If the Pr. 2 setting is higher than the Pr. 13 "Starting frequency" value, note that the motor will
run at the set frequency according to the acceleration time setting by merely switching the start
signal on, without entry of the command frequency.
햲
Screen at powering on
The monitor display appears.
햳
Press the PU/EXT key to choose the PU
operation mode.
햴
Press the MODE key to choose the parameter
setting mode.
햵
Turn the digital dial until P.1 (Pr. 1) appears.
햶
Press the SET key to show the currently set value.
The initial value "120.0" appears.
햷
Turn the digital dial to change it
to the setting value of "50.00".
햸
Press the SET key to set.
Operation
Display
The parameter number read previously appears.
Flicker ... Parameter setting complete!
PRM indication is lit.
앫
By turning the digital dial, you can read another parameter.
앫
Press the SET key to show the setting again.
앫
Press the SET key twice to show the next parameter.
PU indication is lit.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......