Control circuit specifications
Wiring
3 - 26
Safety stop function operation
햲
At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation
panel.
햳
SA is displayed when both of the S1 and S2 signals are in open status and no internal safety circuit
failure exists.
햴
ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
Input Power
Input Signal
Internal
Safety Circuit
햲
Output Signal
Inverter Operation Enable
Signal
S1-PC
S2-PC
SAFE
햴
SAFE2
햴
OFF
—
—
—
OFF
OFF
Output shutoff (Safe state)
ON
Short
Short
No failure
OFF
ON
Drive enabled
Failure
OFF
OFF
Output shutoff (Safe state)
Open
Open
No failure
햳
ON
ON
Output shutoff (Safe state)
Failure
OFF
OFF
Output shutoff (Safe state)
Short
Open
Failure
OFF
OFF
Output shutoff (Safe state)
Open
Short
Failure
OFF
OFF
Output shutoff (Safe state)
Tab. 3-15:
Description of Safety stop function operation
NOTE
For more details, refer to the Safety stop function instruction manual (BCN-A211508-004). (Please
contact your sales representative for the manual.)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......