Operation
Drive the motor
FR-E700 SC EC/ENE
4 - 7
4.2
Drive the motor
The inverter needs frequency command and start command. Refer to the flow chart below to perform
setting.
Check the following items before powering on the inverter:
●
Check that the inverter is installed correctly in a correct place. (Refer to section 2.3.)
●
Check that wiring is correct. (Refer to section 3.2.)
●
Check that no load is connected to the motor.
I001732E
Fig. 4-5:
Steps of operation
NOTES
When protecting the motor from overheat by the inverter, set Pr. 9 "Electronic thermal O/L relay".
(Refer to section 5.1.1.)
When the rated frequency of the motor is 60 Hz, set Pr. 3 "Base frequency" (Refer to section 5.1.2.)
Step of operation
Installation/mounting
Wiring of the power
supply and motor
System examination
How
to give a start
command?
Start command using the PU connector and plug-in
option (communication). (Refer to section 3.5.3.)
Start command with
RUN on the operation
panel (PU).
How to
give a frequency
command?
Connect a switch, relay, etc. to the
control circuit terminal block of the
inverter to give a start command.
(External)
How to
give a frequency
command?
Set from the operation
panel and the PU
(FR-PU04/FR-PU07).
(PU)
(PU)/(External)
(PU)/(External)
(PU)/(External)
Change frequency with
ON/OFF switches
connected to terminals
(multi-speed setting).
Perform frequency setting by a
voltage output device
(connection across terminals 2-
5).
Perform frequency setting by a
current output device
(connection across terminals
4-5).
(Refer to page 5-20)
(Refer to page 5-24)
(Refer to page 5-26)
(Refer to page 5-28)
Set from the operation
panel and the PU
(FR-PU04/FR-PU07).
(PU)/(External)
(External)
(External)
(External)
Change frequency with
ON/OFF switches
connected to terminals
(multi-speed setting).
Perform frequency setting by a
voltage output device
(connection across terminals
2-5).
Perform frequency setting by a
current output device
(connection across terminals
4-5).
(Refer to page 5-30)
(Refer to page 5-32)
(Refer to page 5-35)
(Refer to page 5-39)
RUN
Frequency [Hz]
Time [s]
ON
Start command
Frequency command
Output
frequency
(Refer to page 5-30)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......