Basic settings
External operation
FR-E700 SC EC/ENE
5 - 39
5.3.5
Perform frequency setting by analog current input
An external current source is connection to the frequency inverter for setpoint default setting.
●
Switch terminal STF (STR)-PC on to give a start command.
●
Turn the AU signal on.
●
Pr. 79 "Operation mode selection" must be set to "2" (external operation mode).
I001094E
Fig. 5-29:
Frequency setting by analog current input
NOTE
For the analog current input (0/4 to 20 mA) to become effective for setpoint default setting, the AU
signal on the AU terminal must be activated. This is done, for example, by means of a bridge as
shown in Fig. 5-29.
Power supply
Motor
Inverter
Current signal
source
(0/4–20 mA DC)
Forward rotation start
Reverse rotation start
AU signal
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......