Main circuit connection
Wiring
3 - 10
Cables and wiring length
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will
cause the motor torque to decrease especially at the output of a low frequency.
The following tables indicate a selection example for the wiring length of 20 m.
200 V class (when input power supply is 230 V)
400 V class (when input power supply is 440 V)
햲
The recommended cable size is that of the HIV cable (600 V class 2 vinyl-insulated cable) with
continuous maximum permissible temperature of 75 °C. Assumes that the ambient temperature
is 50 °C or less and the wiring distance is 20 m or less.
햳
The recommended cable size is that of the THHW cable with continuous maximum permissible
temperature of 75 °C. Assumes that the ambient temperature is 40 °C or less and the wiring
distance is 20 m or less.
(Selection example for use mainly in the United States or Canada.)
햴
The recommended cable size is that of the PVC cable with continuous maximum permissible
temperature of 70 °C. Assumes that the ambient temperature is 40 °C or less and the wiring
distance is 20 m or less. (Selection example for use mainly in Europe.)
햵
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/– and P1
and a screw for earthing. (For single-phase power input, the terminal screw size indicates the size
of terminal screw for L1, N, U, V, W, PR, +, – and P1 and a screw for earthing (grounding).)
Applicable Inverter Type
Terminal
Screw
Size
햵
Tightening
Torque
[Nm]
Crimping
Terminal
Cable Size
HIV etc. [mm²]
햲
AWG
햳
PVC [mm²]
햴
L1, N,
P1, +
U, V, W
L1, N,
P1, +
U, V, W
Earth
cable
gauge
L1, N,
P1, +
U, V, W
L1, N,
P1, +
U, V, W
Earth
cable
gauge
FR-E720S-008SC to 030SC
M3.5
1.2
2-3.5
2-3.5
2
2
2
14
14
2.5
2.5
2.5
FR-E720S-050SC
M4
1.5
2-4
2-4
2
2
2
14
14
2.5
2.5
2.5
FR-E720S-080SC
M4
1.5
2-4
2-4
2
2
2
14
14
2.5
2.5
2.5
FR-E720S-110SC
M4
1.5
5.5-4
2-4
3.5
2
2
12
14
4
2.5
2.5
Tab. 3-5:
Cable size
Applicable Inverter Type
Terminal
Screw
Size
햵
Tightening
Torque
[Nm]
Crimping
Terminal
Cable Size
HIV etc. [mm²]
햲
AWG
햳
PVC [mm²]
햴
R/L1,
S/L2,
T/L3,
P1, P/+
U, V, W
R/L1,
S/L2,
T/L3,
P1, P/+
U, V, W
Earth
cable
gauge
R/L1,
S/L2,
T/L3,
P1, P/+
U, V, W
R/L1,
S/L2,
T/L3,
P1, P/+
U, V, W
Earth
cable
gauge
FR-E740-016SC to 095SC
M4
1.5
2-4
2-4
2
2
2
14
14
2.5
2.5
2.5
FR-E740-120SC
M4
1.5
5.5-4
5.5-4 3.5
2
3.5
12
14
4
2.5
4
FR-E740-170SC
M4
1.5
5.5-4
5.5-4
3.5
3.5
3.5
12
12
4
4
4
FR-E740-230SC
M4
1.5
5.5-4
5.5-4
5.5
5.5
5.5 10
10
6
6
10
FR-E740-300SC
M5
2.5
8-5
8-5
8
8
5.5 8
8
10
10
10
Tab. 3-6:
Cable size
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......