Communication operation and setting
Parameter
6 - 240
●
For FR-E700 SC ENE
– The inverter operation after occurrence of a fault in the Ethernet communication line or an
Ethernet board fault can be selected.
– The operation at a communication error can be selected with Pr. 502 when Pr. 851 "Ethernet signal
loss detection function selection" = "3 (initial value)" or Pr. 852 "Ethernet communication check
time interval" "9999" during Ethernet communication.
– When an Ethernet communication error is detected while Pr. 851 "Ethernet signal loss detection
function selection" = "2 or 3 (initial value)", the alarm (LF) signal is output via an output terminal
of the inverter. For the LF signal, set "98 (positive logic) or 198 (negative logic)" in any of Pr. 190 to
Pr. 192 ("Output terminal function selection") to assign the function to the output terminal.
Error definition
Pr. 502
Operation
Indication
Fault Output
Ethernet
communication
line
0 (initial value)
Coasts to stop
E.OP1 lit
Provided
1
Decelerates to stop
E.OP1 lit after stop
Provided after stop
2
Not provided
3
Continued
Normal indication
Ethernet board
0 (initial value), 3
Coasts to stop
E. 1 lit
Provided
1, 2
Decelerates to stop
E. 1 lit after stop
Provided after stop
Tab. 6-69:
Operation at fault occurrence
Error definition
Pr. 502
Operation
Indication
Fault Output
Ethernet
communication
line
0 (initial value)
Kept stopped
E.OP1 lit continued
Kept provided
1
2
Automatic restart
functions
Normal display
Not provided
3
Continued
Ethernet board
0 (initial value), 3
Kept stopped
E. 1 lit continued
Kept provided
1, 2
Tab. 6-70:
Operation at fault removal
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......