Wiring
Electromagnetic compatibility (EMC)
FR-E700 SC EC/ENE
3 - 51
쑶
Example
쑴
Breaker Designed for Harmonic and
Surge Suppression
Standard Breaker
Leakage current Ig1 [mA]
Leakage current Ign [mA]
0 (without noise filter)
Leakage current Igi [mA]
1 (with noise filter)
Leakage current Ig2 [mA]
Motor leakage current Igm [mA]
0.36
Total leakage current [mA]
2.79
6.15
Rated sensitivity current [mA]
30
100
Tab. 3-24:
Estimation of the permanent flowing leakage current
NOTES
The frequency inverter monitors its own output for ground faults up to a frequency of 120 Hz.
However, it is important to understand that this feature only protects the inverter itself. It cannot
be used to provide protection against shock hazards for personnel.
In the connection earthed-neutral system, the sensitivity current is purified against an earth fault
in the inverter output side. Earthing must conform to the requirements of national and local safety
regulations and electrical codes. (JIS, NEC section 250, IEC 536 class 1 and other applicable
standards)
When the breaker is installed on the output side of the inverter, it may be unnecessarily operated
by harmonics even if the effective value is less than the rating. In this case, do not install the
breaker since the eddy current and hysteresis loss will increase, leading to temperature rise.
The following models are standard breakers: BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA and NV-2F
earth leakage relay (except NV-ZHA), NV with AA neutral wire open-phase protection.
The other models are designed for harmonic and surge suppression: NV-C/NV-S/MN series,
NV30-FA, NV50-FA, BV-C2, earth leakage alarm breaker (NF-Z), NV-ZHA, NV-H.
3
Inverter
M
3~
3~, 400 V, 2.2k W
ELB
5.5 mm²
5 m
5.5 mm²
60 m
Ig1
Ign
Igi
Ig2
Igm
Noise filter
(optional)
1
3
---
66
5 m
1000 m
--------------------
0.11
=
1
3
---
66
60 m
1000 m
--------------------
1,32
=
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......