Parameter
Function assignment of external terminals
FR-E700 SC EC/ENE
6 - 117
Input terminal function assignment
햲
When Pr. 59 "Remote function selection" = 1 or 2, the functions of the RL, RM and RH signals are
changed as given in the table.
햳
When Pr. 270 "Stop-on contact control selection" = 1, functions of RL and RT signals are changed
as in the table.
햴
The OH signal turns on when the relay contact "opens".
Setting
Terminal
Function
Related Parameters
Refer to
Page
0
RL
Pr. 59 = 0
(initial value)
Low-speed operation command
Pr. 4–Pr. 6, Pr. 24–Pr. 27,
Pr. 232–Pr. 239
Pr. 59 = 1, 2
햲
Remote setting (setting clear)
Pr. 59
Pr. 270 = 1
햳
Stop-on contact selection 0
Pr. 270, Pr. 275, Pr. 276
1
RM
Pr. 59 = 0
(initial value)
Middle-speed operation command
Pr. 4–Pr. 6, Pr. 24–Pr. 27,
Pr. 232–Pr. 239
Pr. 59 = 1, 2
햲
Remote setting (deceleration)
Pr. 59
2
RH
Pr. 59 = 0
(initial value)
High-speed operation command
Pr. 4–Pr. 6, Pr. 24–Pr. 27,
Pr. 232–Pr. 239
Pr. 59 = 1, 2
햲
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44–Pr. 51
Pr. 270 = 1
햳
Stop-on contact selection 1
Pr. 270, Pr. 275, Pr. 276
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
7
OH
External thermal relay input
햴
Pr. 9
8
REX
15 speed selection (combination with three speeds RL, RM, RH)
Pr. 4–Pr. 6, Pr. 24–Pr. 27,
Pr. 232–Pr. 239
10
X10
Inverter operation enable signal
(FR-HC-, FR-CV connection)
Pr. 30, Pr. 70
12
X12
PU operation external interlock
Pr. 79
14
X14
PID control valid terminal
Pr. 127–Pr. 134
15
BRI
Brake opening completion signal
Pr. 278–Pr. 285
16
X16
PU-external operation switchover
(turning on X16 selects external operation)
Pr. 79, Pr. 340
18
X18
V/F switchover (V/F control is exercised when X18 is on)
Pr. 80, Pr. 81, Pr. 800
24
MRS
Output stop
Pr. 17
25
STOP
Start self-holding selection
—
60
STF
Forward rotation command
(assigned to STF terminal (Pr. 178) only)
—
61
STR
Reverse rotation command
(assigned to STR terminal (Pr. 179) only)
—
62
RES
Inverter reset
—
—
65
X65
PU/NET operation switchover
(turning on X65 selects PU operation)
Pr. 79, Pr. 340
66
X66
External/NET operation switchover
(turning on X66 selects NET operation)
Pr. 79, Pr. 340
67
X67
Command source switchover
(turning on X67 makes Pr. 338 and Pr. 339 commands valid)
Pr. 338, Pr. 339
9999
—
No function
—
—
Tab. 6-27:
Input terminal function assignment
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......