Selection and protection of a motor
Parameter
6 - 88
Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
햲
Motor constants of Mitsubishi high efficiency motor SF-HR.
햳
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
Pr. 71
Pr. 450
Thermal Characteristic of the Electronic Thermal
Relay Function
Motor
Standard
(SF-JR, etc.)
Constant Torque
(SF-JRCA, etc.)
0
(initial value)
Thermal characteristics of a standard motor
✔
—
1
Thermal characteristics of the Mitsubishi constant-torque
motor
✔
40
—
Thermal characteristic of Mitsubishi high efficiency motor
(SF-HR)
✔
햲
50
—
Thermal characteristic of Mitsubishi constant torque motor
(SF-HRCA)
✔
햳
3
—
Standard motor
Select "Offline auto tun-
ing setting"
✔
13
—
Constant-torque motor
✔
23
—
Mitsubishi standard motor
(SF-JR 4P 1.5 kW or less)
✔
43
—
Mitsubishi high efficiency motor
(SF-HR)
✔
햲
53
—
Mitsubishi constant-torque
motor (SF-HRCA)
✔
햳
4
—
Standard motor
Auto tuning data can be
read, changed, and set.
✔
14
—
Constant-torque motor
✔
24
—
Mitsubishi standard motor
(SF-JR 4P 1.5 kW or less)
✔
44
—
Mitsubishi high efficiency motor
(SF-HR)
✔
햲
54
—
Mitsubishi constant-torque
motor (SF-HRCA)
✔
햳
5
—
Standard motor
Star connec-
tion
Direct
input of
motor
con-
stants is
enabled
✔
15
—
Constant-torque motor
✔
6
—
Standard motor
Delta
connection
✔
16
—
Constant-torque motor
✔
—
9999
(initial
value)
Without second applied motor
Tab. 6-9:
Setting of parameter Pr. 71 and Pr. 450
NOTE
For the FR-E740-120SC and 170SC, the Pr. 0 "Torque boost" and Pr. 12 "DC injection brake opera-
tion voltage" settings are automatically changed according to the Pr. 71 setting as follows.
Pr. 71
0, 3–6, 23, 24, 40, 43, 44
1, 13–16, 50, 53, 54
Pr. 0
3%
2%
Pr. 12
4%
2%
Tab. 6-10:
Changes of parameter 0 and 12 related to parameter 71
E
CAUTION:
Set the electronic thermal relay function to the thermal characteristic for the constant-torque
motor when using a geared motor (GM-S, GM-D, GM-SY, GM-HY2 series) to perform Advanced
magnetic flux vector control or General-purpose magnetic-flux vector control.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......