Communication operation and setting
Parameter
6 - 286
IP address (Pr. 805 to Pr. 808)
Enter the IP address of the inverter to be connected to Ethernet in Pr. 805 to Pr. 808.
(Enter the IP address assigned by the network administrator.)
Subnet mask (Pr. 809 to Pr. 812)
Enter the subnet mask of the network to which the inverter belongs in Pr. 809 to Pr. 812.
Default gateway address (Pr. 442 to Pr. 445)
Set the IP address of the default gateway, which is a device connecting the networks, in Pr. 442 to
Pr. 445 to establish a communication between the inverter and the devices outside the inverter net-
work.
Ethernet TCP disconnection time coefficient (Pr. 850)
When the inverter does not receive a packet within the time calculated by multiplying the Pr. 850 set-
ting by 8 in seconds from the devices with the TCP connection established, the connection will be for-
cibly closed.
I003108E
Fig. 6-135:
Setting of the IP address
I003108E
Fig. 6-136:
Setting of the subnet mask
I003108E
Fig. 6-137:
Setting of the default gateway address
I004012E
Fig. 6-138:
Setting of the Ethernet TCP disconnection time coefficient
* * * . * * * . * * * . * * *
Set the value in the first octet in Pr. 805.
Set the value in the second octet in Pr. 806.
Set the value in the third octet in Pr. 807.
Set the value in the fourth octet in Pr. 808.
* * * . * * * . * * * . * * *
Set the value in the first octet in Pr. 809.
Set the value in the second octet in Pr. 810.
Set the value in the third octet in Pr. 811.
Set the value in the fourth octet in Pr. 812.
* * * . * * * . * * * . * * *
Set the value in the first octet in Pr. 442.
Set the value in the second octet in Pr. 443.
Set the value in the third octet in Pr. 444.
Set the value in the fourth octet in Pr. 445.
Normal communication
Connected device
Inverter
Time
Timeout
(connection close)
Pr. 850 setting × 8
(seconds)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......