Control mode
Parameter
6 - 32
6.2 Control
mode
V/F control (initial setting), advanced magnetic flux vector control and general-purpose magnetic flux
vector control are available with the inverter FR-E700SC.
V/F control
It controls frequency and voltage so that the ratio of frequency (f) to voltage (V) is constant when
changing frequency.
Advanced (general-purpose) magnetic flux vector control
●
This control divides the inverter output current into an excitation current and a torque current by
vector calculation and makes voltage compensation to flow a motor current which meets the load
torque. Before operation of a motor in advanced magnetic flux vector control, the self-setting of
motor data must occur.
●
General-purpose magnetic flux vector control is the same function as the FR-E500 series. For other
cases, select advanced magnetic flux vector control.
If the following conditions are not satisfied, select V/F control since malfunction such as insufficient
torque and uneven rotation may occur.
●
The motor capacity should be equal to or one rank lower than the inverter capacity.
●
Motor to be used is any of Mitsubishi standard motor, high efficiency motor (SF-JR, SF-HR 0.2 kW
or more) or Mitsubishi constant torque motor (SF-JRCA four-pole, SF-HRCA 0.2 kW to 15 kW). When
using a motor other than the above (other manufacturer's motor), perform offline auto tuning
without fail.
●
Single-motor operation (one motor run by one inverter) should be performed.
●
Wiring length from inverter to motor should be within 30 m. (Perform offline auto tuning in the
state where wiring work is performed when the wiring length exceeds 30 m.)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......