Wiring
Control circuit specifications
FR-E700 SC EC/ENE
3 - 15
3.4
Control circuit specifications
The functions of the terminals highlighted in grey can be adjusted with parameters 178 to 184 "Input
terminal function assignment" and parameters 190 to 192 "Output terminal function assignment" (re-
fer to section 6.10). The listed settings show the default configuration as shipped, which you can re-
store by resetting to the factory defaults.
Input signals
Terminal
Name
Description
Rated
Specifications
Refer to
Page
C
on
tac
t input
STF
Forward rotation
start
Turn on the STF signal to start
forward rotation and turn it
off to stop.
When the STF
and STR signals
are turned on
simultaneously,
the stop com-
mand is given.
Input resist-
ance: 4.7 k
Voltage at open-
ing:
21 V to 26 V DC
Contacts at
short-circuited:
4 to 6 mA DC
STR
Reverse rotation
start
Turn on the STR signal to start
reverse rotation and turn it off
to stop.
RH, RM, RL
Multi-speed
selection
Multi-speed can be selected according to the
combination of RH, RM and RL signals.
RES
Reset
Used to reset alarm output provided when pro-
tective function is activated.
Turn on the RES signal for more than 0.1s, then
turn it off.
Initial setting is for reset always. By setting Pr. 75,
reset can be set to enabled only at an inverter
alarm occurrence. Recover about 1s after reset is
cancelled.
Ref
er
enc
e point
SD
Contact input com-
mon (sink)
24 V DC power sup-
ply common
A determined control function is activated, if the
corresponding terminal is connected to the ter-
minal SD (sink logic). The SD terminal is isolated
from the digital circuits via opto couplers.
The terminal is isolated from the reference poten-
tial of the analog circuit (terminal 5).
—
—
PC
24 V DC
power supply,
contact input
common
(source)
24 V DC/0.1 A output
With negative logic and control via open collector
transistors (e.g. a PLC) the positive pole of an
external power source must be connected to the
PC terminal. With positive logic the PC terminal is
used as a common reference for the control
inputs. This means that when positive logic is
selected (default setting of the EC units) the cor-
responding control function is activated by con-
necting its terminal to the PC terminal.
Power supply
voltage range:
22 V to
26.5 V DC
Permissible load
current: 100 mA
Saf
e
ty
st
op
S1
Safe stop input
(Channel 1)
S1/S2 are safe stop signals for use with in con-
junction with an approved external safety unit.
Both S1/S2 must be used in dual channel form.
Inverter output is shutoff depending on shorten-
ing/opening between S1 and PC, S2 and PC. In
the initial status, terminal S1 and S2 are shorted
with terminal PC by shortening wire. Remove the
shortening wire and connect the safety relay
module when using the safety stop function.
Input resist-
ance: 4.7 k
Voltage when
contacts are
open:
21 V to 26 V DC
When contacts
are shortcir-
cuited:
4 to 6 mA DC
S2
Safe stop input
(Channel 2)
Tab. 3-9:
Input signals (1)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......