Selection of operation mode and operation location
Parameter
6 - 216
Switching of operation mode by external terminal (X65, X66)
When Pr. 79 = any of "0, 2, 6", the operation mode switching signals (X65, X66) can be used to change
the PU or external operation mode to network operation mode during a stop (during a motor stop or
start command off). (Pr. 79 = "6" switch-over mode can be changed during operation)
When switching between the network operation mode and PU operation mode:
햲
Set Pr. 79 to "0" (initial value) or "6".
햳
Set "10" in Pr. 340 "Communication start-up mode selection".
햴
Set "65" to any of Pr. 178 to Pr. 184 to assign the PU-NET operation switching signal (X65) to the
external terminal.
햵
The operation mode changes to PU operation mode when the X65 signal turns on, or to network
operation mode when the X65 signal turns off.
햲
NET operation mode when the X66 signal is on.
햳
PU operation mode is selected when the X16 signal is off. PU operation mode also when Pr. 550
"NET mode operation command source selection" = 0 (communication option control source) and
the communication option is not fitted.
External operation mode when the X16 signal is on.
Pr. 340
Pr. 79
X65 Signal State
Remarks
ON (PU)
OFF (NET)
10
0
(initial setting)
PU operation
mode
햲
NET operation
mode
햳
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
Fixed to NET operation mode
3 / 4
External/PU combined operation mode
External/PU combined mode fixed
6
PU operation
mode
햲
NET operation
mode
햳
Operation mode can be switched with
operation continued
7
X12 (MRS) ON
Switching among the External and PU op-
eration mode is enabled
햳
Output stop in external operation mode
X12 (MRS) OFF
External operation mode
Forcibly switched to external operation
mode
Tab. 6-58:
Operation mode switching by signal X65
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...