Adjust the output torque (current) of the motor
Parameter
6 - 42
Selection method of general-purpose magnetic flux vector control
Fig. 6-4:
Selection method of general-purpose magnetic flux vector control
NOTES
Uneven rotation slightly increases as compared to the V/F control. It is not suitable for machines
such as grinding machine and wrapping machine which requires less uneven rotation at low
speed.
When a surge voltage suppression filter (FFR-DT) is connected between the inverter and motor,
output torque may decrease.
Perform secure wiring.
(Refer to section 3.2.)
Set the motor. (Pr. 71)
햲
Refer to section 6.8.2, for other settings of Pr. 71.
햳
Refer to section 6.8.3 for offline auto tuning.
Motor
Pr. 71
햲
Remarks
Mitsubishi standard
motor
Mitsubishi high effi-
ciency motor
SF-JR
0
(initial value)
SF-HR
40
Others
3
Offline auto tuning is necessary
햳
Mitsubishi constant-
torque motor
SF-JRCA 4P
1
SF-HRCA 4P
50
Others (SF-JRC, etc.)
13
Offline auto tuning is necessary
햳
Other manufacturer's
standard motor
—
3
Offline auto tuning is necessary
햳
Other manufacturer's
constant-torque motor
—
13
Offline auto tuning is necessary
햳
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to section 6.2.1.)
Set the operation command.
(Refer to section 6.18.1.)
Test run
Set motor capacity (kW) in Pr. 80 "Motor capacity" and the number of motor
poles (number of poles) in Pr. 81 "Number of motor poles".
(V/F control is performed when the setting is "9999" (initial value).
Select the start command and speed command.
1) Start command
–
Operation panel: Setting by pressing the RUN key of the
operation panel
–
External command: Setting by forward rotation or reverse
rotation command (terminal STF or STR)
2) Speed command
–
Operation panel: Setting by pressing the digital dial of the
operation panel
–
External analog command (terminal 2 or 4):
Give a speed command using the analog signal input to
terminal 2 (or terminal 4).
–
Multi-speed command:
The external signals (RH, RM, RL) may also be used to give
speed command.
앫
Perform offline auto tuning. (Pr. 96) (Refer to section 6.8.3.)
앫
Set slip compensation. (Pr. 245, Pr. 246, Pr. 247) (Refer to section 6.3.4.)
Select the control method. (Pr. 800)
(Refer to section 6.3.2.)
Set "30" in Pr. 800 to make general-purpose magnetic flux vector control
valid.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......