Motor brake and stop operation
Parameter
6 - 104
When a high power factor converter (FR-HC) is used and automatic restart after instantaneous
power failure function is made valid.
●
When automatic restart after instantaneous power failure function of both the FR-HC and inverter
is made valid (when a value other than "9999" is set in Pr. 57 "Restart coasting time"), set "2" in Pr. 30.
●
Set Pr. 70 to "0%" (initial value).
●
When the FR-HC detects power failure during inverter operation, the RDY signal turns on, resulting
in the motor coasting. Turning the RDY signal off after power restoration, the inverter detects the
motor speed (depends on the Pr. 162 "Automatic restart after instantaneous power failure selec-
tion") and restarts automatically after instantaneous power failure.
Regenerative brake duty alarm output and alarm signal (RBP signal)
●
[RB] appears on the operation panel and an alarm signal (RBP) is output when 85% of the
regenerative brake duty set in Pr. 70 is reached. If the regenerative brake duty reaches 100% of
the Pr. 70 setting, a regenerative overvoltage (E.OV1 to E.OV3) occurs. Note that [RB] is not
displayed when Pr. 30 = "0".
●
The inverter does not trip even when the alarm (RBP) signal is output.
●
For the terminal used for the RBP signal output, assign the function by setting "7 (positive logic)
or 107 (negative logic)" in any of Pr. 190 to Pr. 192 "Output terminal function selection".
I001566E
Fig. 6-42:
Regenerative overload
NOTES
The MRS signal can also be used instead of the X10 signal.
Refer to section 3.8 for connecting the high-duty brake resistor (FR-ABR), brake unit (FR-BU2), high
power factor converter (FR-HC), and power regeneration common converter (FR-CV).
When terminal assignment is changed using Pr. 178 to Pr. 184 "Input terminal function selection"
and Pr. 190 to Pr. 192 "Output terminal function selection", the other functions may be affected.
Make setting after confirming the function of each terminal.
E
CAUTION:
The value set in Pr. 70 must not exceed the setting of the brake resistor used. Otherwise, the
resistor can overheat.
Regenerative brake
pre-alarm (RBP)
Time
Ratio of the brake
duty to the Pr. 70
setting (%)
OFF
ON
ON
100%
85%
100%: Overvoltage tripping
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......