Parameter
Misoperation prevention and parameter setting restriction
FR-E700 SC EC/ENE
6 - 193
Restarting method when stop was made by pressing the STOP key from the PU during external
operation ("PS" is displayed)
Operation panel
햲
After the motor has decelerated to a stop, turn off the STF or STR signal.
햳
Press the PU/EXT key to change to the PU operation mode. The PU indication is lit. The message
"PS" is cancelled.
햴
Press the PU/EXT key to change to the external operation mode. The EXT indication is lit.
햵
Turn on the STF or STR signal.
Parameter unit (FR-PU04/FR-PU07)
햲
After completion of deceleration to a stop, switch off the STF or STR signal.
햳
Press the EXT key. The message "PS" is cancelled.
햴
Switch on the STF or STR signal.
The motor can be restarted by making a reset using a power supply reset or RES signal.
I000027C
Fig. 6-99:
Stop during external operation
NOTE
If Pr. 250 "Stop selection" is set to other than "9999" to select coasting to a stop, the motor will not
be coasted to a stop but decelerated to a stop by the PU stop function during external operation.
Time
PU key
STOP key
Operation panel
Speed
STF (EIN)
STR (AUS)