Selection and protection of a motor
Parameter
6 - 82
6.8
Selection and protection of a motor
6.8.1
Motor overheat protection (Electronic thermal O/L relay) (Pr. 9, Pr. 51)
The FR-E700SC EC/ENE frequency inverters have an internal electronic motor protection function that
monitors the motor frequency and motor current. Overload conditions are identified and the motor
protection function is triggered on the basis of these two factors, in combination with the rated motor
current. The electronic motor protection function is primarily for protection against overheating at in-
termediate speeds and high motor torques. The reduced cooling performance of the motor fan under
these conditions is also taken into account.
햲
The initial value of the FR-E720S-050SC or less and FR-E740-026SC or less is set to 85% of the
rated inverter current.
햳
The above parameters can be set when Pr. 160 "User group read selection" = 0.
햴
When parameter is read using the FR-PU04, a parameter name different from an actual parameter
is displayed.
Purpose
Parameters that must be set
Refer to
Section
Motor protection from overheat
Electronic thermal O/L relay
Pr. 9, Pr. 51
Use the constant torque motor
Applied motor
Pr. 71, Pr. 450
The motor performance can be maxi-
mized for operation in magnetic flux
vector control method.
Offline auto tuning
Pr. 71,
Pr. 80–Pr. 84,
Pr. 90–Pr. 94,
Pr. 96, Pr. 859
Pr.
No.
Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to Sec-
tion
9
Electronic thermal O/L relay
Rated inverter
current
햲
0–500 A
Set the rated motor current.
71
72
178–184
190–192
Applied motor
PWM frequency
selection
Input terminal function
selection
Output terminal
function selection
51
Second electronic
thermal O/L relay
햳 햴
9999
0–500 A
Made valid when the RT signal is on.
Set the rated motor current.
9999
Second electronic thermal O/L relay
invalid
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......