Electric Shock Prevention
P
WARNING:
●
While power is on or when the inverter is running, do not open the front cover. Otherwise you
may get an electric shock.
●
Do not run the inverter with the front cover removed. Otherwise, you may access the exposed
high-voltage terminals or the charging part of the circuitry and get an electric shock.
●
Even if power is off, do not remove the front cover except for wiring or periodic inspection.
You may access the charged inverter circuits and get an electric shock.
●
Before starting wiring or inspection, check to make sure that the operation panel indicator
is off, wait for at least 10 minutes after the power supply has been switched off, and check
that there are no residual voltage using a tester or the like. The capacitor is charged with
high voltage for some time after power off and it is dangerous.
●
This inverter must be earthed. Earthing must conform to the requirements of national and
local safety regulations and electrical codes. (JIS, NEC section 250, IEC 536 class 1 and other
applicable standards)
Use a neutral-point earthed (grounded) power supply for 400 V class inverter in compliance
with EN standard.
●
Any person who is involved in the wiring or inspection of this equipment should be fully
competent to do the work.
●
Always install the inverter before wiring. Otherwise, you may get an electric shock or be
injured.
●
If your application requires by installation standards an RCD (residual current device) as up
stream protection please select according to DIN VDE 0100-530 as following:
Single phase inverter type A or B
Three phase inverter only type B
●
Perform setting dial and key operations with dry hands to prevent an electric shock. Other-
wise you may get an electric shock.
●
Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise
you may get an electric shock.
●
Do not replace the cooling fan while power is on. It is dangerous to replace the cooling fan
while power is on.
●
Do not touch the printed circuit board with wet hands. You may get an electric shock.
●
When measuring the main circuit capacitor capacity, the DC voltage is applied to the motor
for 1 s at powering off. Never touch the motor terminal, etc. right after powering off to
prevent an electric shock.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......