Operation selection at power failure
Parameter
6 - 160
Frequency search gain (Pr. 298), offline auto tuning (Pr. 96)
When automatic restart after instantaneous power failure operation (with frequency search) is valid
at V/F control, perform offline auto tuning. Perform offline auto tuning during V/F control in the fol-
lowing order to set Pr. 298 "Frequency search gain" automatically. (Refer to page 6-90 during ad-
vanced magnetic flux vector control and general-purpose magnetic flux vector control.)
Before performing offline auto tuning
Check the following before performing offline auto tuning:
●
The inverter is under V/F control.
●
A motor should be connected. Note that the motor should be at a stop at a tuning start.
●
The motor capacity should be equal to or one rank lower than the inverter capacity.
●
A high-slip motor, high-speed motor and special motor cannot be tuned.
(The maximum frequency is 120 Hz.)
●
Even if tuning is performed without motor running (Pr. 96 "Auto tuning setting/status" = "21"), the
motor may run slightly. Therefore, fix the motor securely with a mechanical brake, or before tuning,
make sure that there will be no problem in safety if the motor runs (caution is required especially
in vertical lift applications). Note that tuning performance is unaffected even if the motor runs
slightly.
●
Offline auto tuning will not be performed properly if it is performed with a surge voltage
suppression filter (FFR-DT) connected between the inverter and motor. Remove it before starting
tuning.
Setting
●
Set "21" in Pr. 96 "Auto tuning setting/status". Tuning is performed without motor running.
According to the motor type and the inverter capacity, it takes approximately 9 s until tuning is
completed. (Excitation noise is produced during tuning.)
●
Set the rated motor current (initial value is rated inverter current) in Pr. 9 "Electronic thermal O/L
relay". (Refer to section 6.8).
●
Set Pr. 71 "Applied motor" according to the motor used.
햲
Refer to section 6.8.2, for other settings of Pr. 71.
Motor
Pr. 71
햲
Mitsubishi standard motor,
Mitsubishi high efficiency motor
SF-JR
3
SF-JR 4P-1.5 kW or less
23
SF-HR
43
Others
3
Mitsubishi constant-torque motor
SF-JRCA 4P
13
SF-HRCA
53
Others (SF-JRC, etc.)
13
Other manufacturer's standard motor
—
3
Other manufacturer's constant torque motor
—
13
Tab. 6-41:
Motor selection
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......