Operation selection at power failure
Parameter
6 - 166
Power failure stop mode (Pr. 261 = 1)
If power is restored during power failure deceleration, deceleration to a stop is continued and the in-
verter remains stopped. To restart, turn off the start signal once, then turn it on again.
I001815E
Fig. 6-83:
Power restoration
NOTES
When automatic restart after instantaneous power failure is selected (Pr. 57
9999), power failure
stop function is made invalid and automatic restart operation after instantaneous power failure is
made valid.
When the power failure deceleration stop function is active (Pr. 261 = "1"), the inverter will not start
even if the power is turned ON with the start signal (STF/STR) ON. After switching on the power,
turn off the start signal once and then on again to make a start.
I001175E
Fig. 6-84:
Restart at power restoration
Output
frequency
Power
supply
During deceleration at
occurrence of power failure
During stop at
occurrence of
power failure
Time
Turn off STF once to make acceleration again
Output
frequency
Power supply
ON
Not started as inverter is
stopped due to power
failure
OFF
ON
ON
STF
Y46
Time