Parameter
Frequency setting by external terminals
FR-E700 SC EC/ENE
6 - 63
6.6.2
Jog operation (Pr. 15, Pr. 16)
Jog operation is used to setup the machine.The frequency and acceleration/deceleration time for Jog
operation can be set. As soon as the frequency inverter receives the start signal, the motor is accel-
erated at the frequency entered in parameter 15 (jog frequency) using the preset acceleration/brake
time (parameter 16). Jog operation can be performed in either of the external and the PU operation
mode.
These parameters are displayed as simple mode parameter only when the parameter unit (FR-PU04/
FR-PU07) is connected. When the parameter unit is not connected, the above parameters can be set
when Pr. 160 "User group read selection" = 0.
Jog operation from outside
When the jog signal is on, a start and stop can be made by the start signal (STF, STR). For the terminal
used for Jog operation selection, set "5" in any of Pr. 178 to Pr. 184 "Input terminal function selection"
to assign the function.
Pr. No. Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
15
Jog frequency
5 Hz
0–400 Hz
Set the frequency for jog operation.
13
29
20
21
79
178–184
Starting frequency
Acceleration/
deceleration pattern
selection
Acceleration/
deceleration reference
frequency
Acceleration/
deceleration time
increments
Operation mode
selection
Input terminal
function selection
16
Jog acceleration/
deceleration time
0.5 s
0–3600/360 s
Acceleration/deceleration time for jog operation.
This setting is related to to the reference frequency set
in Pr. 20 and the increments set in Pr. 21.
Pr. 21 = 0 (Initial setting)
Setting range: 0–3600 s
Increments: 0.1s
Pr. 21 = 1
Setting range: 0–360 s
Increments: 0.01 s
The acceleration and deceleration times cannot be set
separately.
I001788E
Fig. 6-20:
Connection diagram for external jog operation
Power
supply
Forward rotation start
Reverse rotation start
Jog operation
Motor
Inverter
햲
When assigning the jog signal to the
terminal RH
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......