Parameter
Acceleration and deceleration
FR-E700 SC EC/ENE
6 - 77
6.7.3
Acceleration and deceleration pattern (Pr. 29)
You can set the acceleration/deceleration pattern suitable for application.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Linear acceleration/deceleration (Pr. 29 = "0", initial value)
For the inverter operation, the output frequency is made to change linearly (linear acceleration/de-
celeration) to prevent the motor and inverter from excessive stress to reach the set frequency during
acceleration, deceleration, etc. when frequency changes. Linear acceleration/deceleration has a uni-
form frequency/time slope (refer to 6-33).
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
29
Acceleration/deceleration
pattern selection
0
0
Linear acceleration/deceleration
3
7
8
20
Base frequency
Acceleration time
Deceleration time
Acceleration/
deceleration reference
frequency
1
S-pattern acceleration/deceleration A
2
S-pattern acceleration/deceleration B
Fig. 6-33:
Characteristic for parameter 29 = "0"
I000015C
Output fr
equenc
y
Time
linear