Frequency setting by analog input (terminal 2, 4)
Parameter
6 - 178
Selection of analog input specifications
For the terminal 2 for analog voltage input, 0 to 5 V (initial value) or 0 to 10 V can be selected. Either
voltage input (0 to 5 V, 0 to 10 V) or current input (4 to 20 mA initial value) can be selected for terminal
4 used for analog input. Change the input specifications by setting Pr. 73 and Pr. 267 and voltage/cur-
rent input switch.
Rated specifications of terminal 4 change according to the voltage/current input switch setting:
Voltage input: Input resistance 10 k
1 k , maximum permissible input voltage 20 V DC
Current input: Input resistance 233
5 , maximum permissible current 30 mA
Fig. 6-90:
Voltage/current input switch
I002131E
E
CAUTION:
Set Pr. 267 and a voltage/current input switch correctly, then input an analog signal in accord-
ance with the setting. Incorrect setting as in the table below could cause component damage.
Incorrect settings other than below can cause abnormal operation.
Current input
(initial setting)
Voltage input
Setting Causing Component Damage
Operation
Switch Setting
Terminal Input
I
(current input)
Voltage input
This could cause component damage to the analog signal
output circuit of signal output devices.
(electrical load in the analog signal output circuit of signal
output devices increases)
V
(voltage input)
Current input
This could cause component damage of the inverter sig-
nal input circuit.
(output power in the analog signal output circuit of signal
output devices increases)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......