Parameter
Monitor display and monitor output signals
FR-E700 SC EC/ENE
6 - 147
You can select the decimal digits of the monitor (Pr. 268)
As the operation panel display is 4 digits long, the decimal places may vary at analog input, etc. The
decimal places can be hidden by selecting the decimal digits. In such a case, the decimal digits can be
selected by Pr. 268.
Pr. 268
Description
9999 (initial value)
No function
0
For the first or second decimal places (0.1 increments or 0.01 increments) of the mon-
itor, numbers in the first decimal place and smaller are rounded to display an integral
value (1 increments).
The monitor value smaller than 0.99 is displayed as 0.
1
When 2 decimal places (0.01 increments) are monitored, the 0.01 decimal place is
dropped and the monitor displays the first decimal place (0.1 increments).
The monitored digits in 1 increments are displayed as they are.
Tab. 6-39:
Selection of decimal digits
NOTE
The number of display digits on the cumulative energization time (Pr. 52 = "20"), actual operation
time (Pr. 52 = "23") and cumulative power (Pr. 52 = "25") does not change.