Installation
Enclosure design
FR-E700 SC EC/ENE
2 - 11
2.4.2 Inverter
placement
Clearances around the inverter
Always observe the specified minimum clearances to ensure good heat dissipation and adequate ac-
cessibility of the frequency inverter for servicing.
Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
Above the inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed
above the inverter should be heat resistant.
I002152E
Fig. 2-10:
Clearances
Ambient temperature and humidity
Clearances (side)
Clearances (front)
Leave enough clearances and take cooling
measures.
In
ve
rt
e
r
5 cm
5 cm
5cm
10 cm
10 cm
1 cm
햲
1 cm
햲
x = Measurement
position
In
ve
rt
e
r
Temperature: 10 °C to +50 °C
Humidity: 90% RH maximum
1 cm
햲
햲
When using the inverters at the ambient
temperature of 40 °C or less, the inverters can
be installed without any clearance between
them (0 cm clearance).
When ambient temperature exceeds 40 °C,
clearances between the inverters should be
1 cm or more (5 cm or more for the FR-E740-
120SC or more).
햲
5cm for the FR-E740-120SC and
more
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......