Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 263
●
Inverter status monitor
햲
The signal within parentheses is the initial setting. The description changes depending on the
setting of Pr. 190 to Pr. 192 "Output terminal function selection". (Refer to section 6.10.5.)
Item
Instruction
Code
Bits
Description
Example
Inverter
status
monitor
H7A
8
b0: RUN (inverter running)
햲
b1: Forward rotation
b2: Reverse rotation
b3: SU (up to frequency)
b4: OL (overload)
b5: —
b6: FU (frequency
detection)
햲
b7: ABC (alarm)
햲
Inverter
status
monitor
(extended)
H79
16
b0: RUN (inverter running)
햲
b1: Forward rotation
b2: Reverse rotation
b3: SU (up to frequency)
b4: OL (overload)
b5: —
b6: FU (frequency
detection)
햲
b7: ABC (alarm)
햲
b8: —
b9: —
b10: —
b11: —
b12: —
b13: —
b14: —
b15: Alarm occurrence
Tab. 6-84:
Monitoring the inverter status
Example 1: H02 (During forward rotation)
Example 2: H80 (Stop at alarm occurrence)
Example 1: H0002 (During forward rotation)
Example 2: H8080 (Stop at alarm occurrence)