Parameter
CC-Link IE Field Network Basic
FR-E700 SC EC/ENE
6 - 351
I/O signal list
●
When Pr. 544 = "0" (compatible with CC-Link Ver.1)
– Remote I/O (32 points)
햲
These signals are set in the initial status. Using Pr. 180 to Pr. 184, you can change input signal
functions. For the details of Pr. 180 to Pr. 184, refer to page 6-116.
햳
The signals are fixed. They cannot be changed using parameters.
햴
These signals are set in the initial status. Using Pr. 190 to Pr. 192, you can change output signal
functions. For the details of Pr. 190 to Pr. 192 refer to page 6-126.
햵
Functions assigned to Pr. 313 to Pr. 315 are activated. For the assignable functions, refer to the
description of Pr. 190 to Pr. 192 on page 6-126.
햶
"n" indicates a value determined according to the station number setting.
Device
No.
Signal
Refer to
page
RYn0
Forward rotation command
RYn1
Reverse rotation command
RYn2
High-speed operation command
(terminal RH function)
RYn3
Middle-speed operation command
(terminal RM function)
RYn4
Low-speed operation command
(terminal RL function)
RYn5
Not used
—
RYn6
Second function selection (RT signal)
RYn7
Terminal 4 input selection (AU signal)
RYn8
Not used
—
RYn9
Output stop (terminal MRS function)
RYnA
Not used
—
RYnB
Reset (terminal RES function)
RYnC
Monitor command
RYnD
Frequency setting command (RAM)
RYnE
Frequency setting command (RAM, E²PROM)
RYnF
Instruction code execution request
RY(n+1)0
to
RY(n+1)7
Reserved
—
RY(n+1)8 Not used (initial data process completion flag)
RY(n+1)9 Not used (initial data process request flag)
RY(n+1)A Error reset request flag
RY(n+1)B
to
RY(n+1)F
Reserved
—
Tab. 6-144:
Remote outputs
Device
No.
Signal
Refer to
page
RXn0
Forward running
RXn1
Reverse running
RXn2
Inverter running (terminal RUN function)
RXn3
Up to frequency (SU signal)
RXn4
Overload alarm (OL signal)
RXn5
Not used
—
RXn6
Frequency detection (terminal FU function)
RXn7
Fault (terminal ABC function)
RXn8
Not used
—
RXn9
Pr. 313 assignment function (DO0)
RXnA
Pr. 314 assignment function (DO1)
RXnB
Pr. 315 assignment function (DO2)
RXnC
Monitoring
RXnD
Frequency setting completion (RAM)
RXnE
Frequency setting completion (RAM, E²PROM)
RXnF
Instruction code execution completion
RX(n+1)0
to
RX(n+1)7
Reserved
—
RX(n+1)8 Not used (initial data process request flag)
RX(n+1)9 Not used (initial data process completion flag)
RX(n+1)A Error status flag
RX(n+1)B Remote station ready
RX(n+1)C
to
RX(n+1)F
Reserved
—
Tab. 6-145:
Remote inputs
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......