Selection of operation mode and operation location
Parameter
6 - 206
6.18
Selection of operation mode and operation location
6.18.1
Operation mode selection (Pr. 79)
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external op-
eration), operation from the operation panel and PU (FR-PU04/FR-PU07) (PU operation), combined
operation of PU operation and external operation (external/PU combined operation), and network
operation (when RS-485 communication or a communication option is used).
The above parameter can be changed during a stop in any operation mode.
Purpose
Parameters that must be set
Refer to
Section
Operation mode selection
Operation mode selection
Pr. 79
Started in network operation mode
Operation mode at power on
Pr. 79, Pr. 340
Selection of control source
Selection of control source, speed com-
mand source and control location during
communication operation
Pr. 338, Pr. 339,
Pr. 550, Pr. 551
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
79
Operation mode selection
0
0
External/PU switchover mode
External operation mode at power on
15
4–6
24–27
232–239
75
161
178–184
190–192
340
550
Jog frequency
Multi-speed operation
Reset selection/
disconnected PU
detection/PU stop
selection
Frequency setting/
key lock operation
selection
Input terminal function
selection
Output terminal function
selection
Communication start-up
mode selection
NET mode operation
command source
selection
1
Fixed to PU operation mode
2
Fixed to external operation mode
Operation can be performed by switching between
external and NET operation mode
3
Combined operation mode 1
Running frequency:
Operation panel, and PU (FR-PU04/FR-PU07) setting
or external signal input [multi-speed setting, across
terminals 4-5 (valid when AU signal turns on)]
Start signal:
External signal input (terminal STF, STR)
4
External/PU combined operation mode 2
Running frequency:
External signal input (terminal 2, 4, JOG, multi-speed
setting, etc.)
Start signal:
Enter from the RUN key of the operation panel and
the FWD/REV keys of the PU (FR-PU04/FR-PU07)
6
Switchover mode
Switchover between PU operation, external
operation, and NET operation is available while
keeping the same operation status.
7
External operation mode (PU operation interlock)
X12 signal ON:
Operation mode can be shifted to PU operation mode
(output stop during external operation)
X12 signal OFF:
Operation mode can not be switched to PU operation
mode.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......