Special operation
Parameter
6 - 298
Connection diagram
The following graphic shows a typical application:
햲
The power supply must be selected in accordance with the power specifications of the detector
used.
햳
The used input signal terminal changes depending on the Pr. 178 to Pr. 184 "Input terminal
selection" setting.
햴
The used output signal terminal changes depending on the Pr. 190 to Pr. 192 "Output terminal
selection" setting.
햵
The AU signal need not be input.
I002137C
Fig. 6-152:
Connection diagram in source logic
Power
supply
Forward rotation
Reverse rotation
PID control
selection
Setting
Potentiometer
1 k , 1–2 W
(Set point
setting)
Measured value 4–20 mA
Pump
2 wire type
Det
e
ct
or
Upper limit
Lower limit
Power supply for OC outputs
햲
햳
햳
햳
햴
햴
Pr. 128 = 20
Pr. 182 = 14
Pr. 190 = 15
Pr. 191 = 14
Pr. 192 = 16
1 phase,
e. g. 230 V, 50 Hz
햵