Basic settings
Simple mode parameter list
FR-E700 SC EC/ENE
5 - 11
5.1.6
Operation mode (Pr. 79)
Select the operation command location and frequency command location.
햲
For the terminal used for the X12 signal (PU operation interlock signal) input, assign "12" in
Pr. 178 to Pr. 184 "Input terminal function selection" to assign functions. For Pr. 178 to Pr. 184,
refer to section 6.10.1. When the X12 signal is not assigned, function of the MRS signal switches
from MRS (output stop) to PU operation interlock signal.
Pr. No. Name
Initial
Value
Setting
Range
Description
LED Indication
79
Operation
mode selection
0
0
External/PU switch over mode
Press the PU/EXT key to switch between the PU and external
operation mode. (Refer to section 4.3.3.)
At power on, the inverter is in the external operation mode.
1
PU operation mode
2
Fixed to external operation mode
Operation can be performed by switching between the external and
Net operation mode.
3
External/PU combined operation mode 1
Running frequency
Start signal
Operation panel and PU (FR-
PU04/FR-PU07) setting or
external signal input (multi-
speed setting, across terminals 4-
5 (valid when AU signal turns
on)).
External signal input
(terminal STF-, STR)
4
External/PU combined operation mode 2
Running frequency
Start signal
External signal input (Terminal 2,
4, JOG, multi-speed selection,
etc.)
Input using the RUN-key of the
operation panel or FWD/REV of
the PU (FR-PU04/FR-PU07)
6
Switch-over mode
Switch among PU operation, external operation, and NET operation
while keeping the same operation status.
7
External operation mode (PU operation interlock)
X12 signal ON
햲
:
Operation mode can be switched to the PU operation mode.
(output stop during external operation)
X12 signal OFF
햲
:
Operation mode can not be switched to the PU operation mode.
NOTE
Setting value "1" to "4" can be changed in the easy operation mode. (Refer to section 4.3.3.)
: OFF
: ON
External operation mode
PU operation mode
External operation mode
NET operation mode
External operation mode
NET operation mode
PU operation mode
External operation mode
PU operation mode
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......