Control circuit specifications
Wiring
3 - 16
Terminal
Name
Description
Rated
Specifications
Refer to
Page
Fr
equenc
y setting
10
(Output
voltage
5 V DC)
Frequency setting
power supply
Used as power supply when connecting potenti-
ometer for frequency setting (speed setting) from
outside of the inverter.
Rated output voltage: 5 V DC
Recommended potentiometer: 1 k , 2 W linear,
multi turn potentiometer
5.2 V DC ± 0.2 V,
Permissible load
current 10 mA
2
Frequency setting
(voltage)
Inputting 0 to 5 V DC (or 0 to 10 V) provides the
maximum output frequency at 5 V (10 V) and
makes input and output proportional. Use Pr. 73
to switch from among input 0 to 5 V DC (initial
setting), 0 to 10 V DC.
Input resistance:
10 k ± 1 k
Maximum
permissible
voltage:
20 V DC
4
Frequency setting
(current)
Inputting 4 to 20 mA DC (or 0 to 5 V, 0 to 10 V)
provides the maximum output frequency at 20
mA and makes input and output proportional.
This input signal is valid only when the AU signal
is on (terminal 2 input is invalid).
To use terminal 4 (initial setting is current input),
set "4" to any of Pr. 178 to Pr. 184 (input terminal
function selection), and turn AU signal ON.
Use Pr. 267 to switch from among input 4 to
20 mA (initial setting), 0 to 5 V DC and 0 to
10 V DC. Set the voltage/current input switch in
the "V" position to select voltage input (0 to 5 V/0
to 10 V).
Current input:
Input resistance:
233 ± 5
Maximum
permissible cur-
rent: 30 mA
Voltage input:
Input resistance:
10 k ± 1 k
Maximum
permissible
voltage:
20 V DC
5
Frequency setting
common
Terminal 5 provides the common reference
potential (0 V) for all analog set point values and
for the analog output signals AM (voltage). The
terminal is isolated from the digital circuit’s refer-
ence potential (SD). This terminal should not be
grounded. If local regulations require grounding
of the reference potential note that this can prop-
agate any noise in the ground potential to the
control electronics, thus increasing sensitivity to
interference.
—
Tab. 3-9:
Input signals (2)
NOTE
Set Pr. 267 and a voltage/current input switch correctly, then input analog signals in accordance
with the settings.
Applying a voltage with voltage/current input switch in "I" position (current input is selected) or a
current with switch in "V" position (voltage input is selected) could cause component damage of
the inverter or analog circuit of output devices. Refer to section 6.16 for details.
Voltage input
Current input
(initial status)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......