MODBUS®/TCP (FR-E700 SC ENE)
Parameter
6 - 348
●
Faults history
Register
Definition
Read/write
Remarks
40501
Faults history 1
Read/write
Being 2 bytes in length, the data is stored as "H00
첸첸
".
Refer to the lowest 1 byte for the error code. (Refer to the
following table for the error codes.)
Performing write using the register 40501 batch-clears
the faults history.
Set any value as data.
40502
Faults history 2
Read
40503
Faults history 3
Read
40504
Faults history 4
Read
40505
Faults history 5
Read
40506
Faults history 6
Read
40507
Faults history 7
Read
40508
Faults history 8
Read
Tab. 6-138:
Faults history
Daten
Beschreibung
Daten
Beschreibung
Daten
Beschreibung
H00
No fault present
H70
E.BE
HC7
E.AIE
H10
E.OC1
H80
E.GF
HC8
E.USB
H11
E.OC2
H81
E.LF
HC9
E.SAF
H12
E.OC3
H90
E.OHT
HD8
E.MB4
H20
E.OV1
HA0
E.OPT
HD9
E.MB5
H21
E.OV2
HA1
E.OP1
HDA
E.MB6
H22
E.OV3
HB0
E.PE
HDB
E.MB7
H30
E.THT
HB1
E.PUE
HF1
E.1
H31
E.THM
HB2
E.RET
HF5
E.5
H40
E.FIN
HB3
E.PE2
HF6
E.6
H52
E.ILF
HC0
E.CPU
HF7
E.7
H60
E.OLT
HC5
E.IOH
HFD
E.13
Tab. 6-139:
Error code list
NOTES
For the details of the faults, refer to section 7.1.
When a 32-bit parameter setting or monitor item is read and the value to be read exceeds HFFFF,
HFFFF is returned.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......