Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 239
Fig. 6-121:
Operation when Pr. 502 setting is "2"
I001836E
NOTES
The fault output indicates fault output signal (ALM signal) or alarm bit output.
When the setting was made to provide a fault output, the fault description is stored into the faults
history. (The fault description is written to the faults history when a fault output is provided.)
When no fault output is provided, the fault definition overwrites the fault indication of the faults
history temporarily, but is not stored. After the fault is removed, the fault indication returns to the
ordinary monitor, and the faults history returns to the preceding fault indication.
When the Pr. 502 setting is "1" or "2", the deceleration time is the ordinary deceleration time set-
ting (e.g. Pr. 8, Pr. 44, Pr. 45). In addition, acceleration time for restart is the normal acceleration
time (e.g. Pr. 7, Pr. 44).
When "2" is set in Pr. 502, run command/speed command at restarting follows the command
before an fault occurrence.
When "2" is set in Pr. 502 at occurrence of a communication error and the error is removed during
deceleration, the inverter accelerates again at that point.
Communication
fault
Display
OFF
Fault
occurrence
Output fr
equenc
y
Fault display
(E.PUE)
Fault output
(ALM)
ON
Fault
removal
Decelerates to
stop
OFF
OFF
Time
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......