Parameter
Function assignment of external terminals
FR-E700 SC EC/ENE
6 - 131
6.10.6
Detection of output frequency (SU, FU, Pr. 41 to Pr. 43)
The inverter output frequency is detected and output to the output signal.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
Up-to-frequency sensitivity (SU, Pr. 41)
When the output frequency reaches the set frequency, the up-to-frequency signal (SU) is output. The
Pr. 41 value can be adjusted within the range 0% to ±100% on the assumption that the set frequency
is 100%.
This parameter can be used to ensure that the running frequency has been reached to provide the op-
eration start signal etc. for related equipment.
When using the SU signal, set "1 (positive logic) or 101 (negative logic)" in Pr. 190 to Pr. 192 "Output
terminal function selection" to assign function to the output terminal.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
41
Up-to-frequency sensitivity
10%
0–100%
Set the level where the SU signal turns on.
190–192 Output terminal
function selection
42
Output frequency detection
6 Hz
0–400 Hz
Set the frequency where the FU signal turns on.
43
Output frequency detection for
reverse rotation
9999
0–400 Hz
Set the frequency where the FU signal turns on in
reverse rotation.
9999
Same as Pr. 42 setting
Fig. 6-61:
Output of the SU signal
I000020C
Adjustment
range
Pr. 41
SU
signal
Output
fr
equenc
y
Set
frequency
Running frequency
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......