Specifications
Appendix
A - 2
A.1.2
3-phase, 400 V class
햲
The applied motor capacity indicated is the maximum capacity applicable for use of the
Mitsubishi 4-pole standard motor.
햳
The rated output capacity indicated assumes that the output voltage is 440 V.
햴
Setting 2 kHz or more in Pr. 72 "PWM frequency selection" to perform low acoustic noise operation
with the ambient temperature exceeding 40 °C, the rated output current is the value in parenthe-
ses.
햵
The % value of the overload current rating indicated is the ratio of the overload current to the
inverter’s rated output current. For repeated duty, allow time for the inverter and motor to return
to or below the temperatures under 100% load.
햶
The maximum output voltage does not exceed the power supply voltage. The maximum output
voltage can be changed within the setting range. However, the pulse voltage value of the inverter
output side voltage remains unchanged at about
冑
2 that of the power supply.
햷
The braking torque indicated is a short-duration average torque (which varies with motor loss)
when the motor alone is decelerated from 60 Hz in the shortest time and is not a continuous
regenerative torque. When the motor is decelerated from the frequency higher than the base
frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake
resistor, use the optional brake resistor when regenerative energy is large. A brake unit (FR-BU2)
may also be used.
햸
The power supply capacity varies with the value of the power supply side inverter impedance
(including those of the input reactor and cables).
Model FR-E740-
첸첸첸
SC EC/ENE
016
026
040
060
095
120
170
230
300
Rated motor capacity [kW]
햲
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Output
Rated capacity [kVA]
햳
1.2
2.0
3.0
4.6
7.2
9.1
13.0
17.5
23.0
Rated current [A]
햴
1.6
(1.4)
2.6
(2.2)
4.0
(3.8)
6.0
(5.4)
9.5
(8.7)
12.0
17.0
23.0
30.0
Overload current rating
햵
200% of rated motor capacity for 3 s; 150% for 60 s
Voltage
햶
3-phase AC, 0 V to power supply voltage
Regenerative braking torque
햷
100%
50%
20%
Po
w
er supply
Power supply voltage
3-phase, 380–480 V AC, 15%/+10%
Voltage range
325–528 V AC at 50/60 Hz
Power supply frequency
50/60 Hz ± 5%
Rated input capacity [kVA]
햸
1.5
2.5
4.5
5.5
9.5
12.0
17.0
20.0
28.0
Protective structure
IP20
Cooling system
Self cooling
Forced air cooling
Weight [kg]
1.4
1.4
1.9
1.9
1.9
3.2
3.2
6.0
6.0
Tab. A-2:
Specifications
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......