Control circuit specifications
Wiring
3 - 28
NOTES
Using the SOURCE/SINK jumper (and the particular connection of the PC/SD terminal as a refer-
ence point), the input terminals can be changed between positive switching (source logic) or neg-
ative switching (sink logic) depending on regional requirements.
Turn off the inverter power before switching a jumper connector.
The sink-source logic change-over jumper connector must be fitted in only one of those positions.
If it is fitted in both positions at the same time, the inverter may be damaged.
The capacity plate is placed on the front cover and the rating plate is on the inverter. Since these
plates have the same serial numbers, always reinstall the removed cover onto the original inverter.
Terminal PC is always the common terminal for the safety stop input terminals (S1 and S2) of the
inverter with safety stop function regardless of sink/source logic.