Parameter
Function assignment of external terminals
FR-E700 SC EC/ENE
6 - 127
You can set the functions of the output terminals.
Refer to the following table and set the parameters:
0–99: Source
logic
100–199: Sink
logic
Setting
Terminal
Function
Operation
Related Parameters
Refer to
Page
Source
Logic
Sink
Logic
0
100
RUN
Inverter running
Output during operation when
the inverter output frequency
rises to or above Pr. 13 "Starting
frequency".
—
1
101
SU
Up to frequency
햲
Output when the output fre-
quency is reached to the set fre-
quency.
Pr. 41
3
103
OL
Overload alarm
Output while stall prevention
function is activated.
Pr. 22, Pr. 23, Pr. 66
4
104
FU
Output frequency detection
Output when the output
frequency reaches the
frequency setting in Pr. 42
(Pr. 43 for reverse rotation).
Pr. 42, Pr. 43
7
107
RBP
Regenerative brake prealarm
Output when 85% of the regen-
erative brake duty set in Pr. 70 is
reached.
Pr. 70
8
108
THP
Electronic thermal O/L relay
pre-alarm
Output when the electronic
thermal relay function cumula-
tive value reaches 85%.
(Electronic thermal relay func-
tion protection (E.THT/E.THM)
activates, when the value
reached 100%.)
Pr. 9
11
111
RY
Inverter operation ready
Output when the inverter can
be started by switching the
start signal on or while it is run-
ning.
—
12
112
Y12
Output current detection
Output when the output cur-
rent is higher than the Pr. 150
setting for longer than the time
set in Pr. 151.
Pr. 150, Pr. 151
13
113
Y13
Zero current detection
Output when the output power
is lower than the Pr. 152 setting
for longer than the time set in
Pr. 153.
Pr. 152, Pr. 153
14
114
FDN
PID lower limit
Output when the feedback
value falls below the lower limit
of PID control.
Pr. 127–Pr. 134
15
115
FUP
PID upper limit
Output when the feedback
value rises above the upper
limit of PID control.
16
116
RL
PID forward/reverse rotation
output
Output when forward rotation
is performed in PID control.
20
120
BOF
Brake opening request
Output to open the brake when
the brake sequence function is
selected.
Pr. 278–Pr. 283,
Pr. 292
25
125
FAN
Fan fault output
Output at the time of a fan
fault.
Pr. 244
26
126
FIN
Heatsink overheat prealarm
Output when the heatsink tem-
perature reaches about 85% of
the heatsink overheat protec-
tion providing temperature.
—
46
146
Y46
During deceleration at occurrence
of power failure (retained until
release)
Output when the power failure-
time deceleration function is
executed.
Pr. 261
47
147
PID
During PID control activated
Output during PID control.
Pr. 127–Pr. 134
64
164
Y64
During retry
Output during retry processing. Pr. 65–Pr. 69
Tab. 6-31:
Output terminal function assignment (1)
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......