Monitor display and monitor output signals
Parameter
6 - 138
6.11
Monitor display and monitor output signals
6.11.1
Speed display and speed setting (Pr. 37)
You can output RPM rates, speeds and throughput volumes based on the output frequency to the dis-
plays of the operation panels, FR-PU04 and FR-PU07 parameter units or to the AM output.
The above parameters can be set when Pr. 160 "User group read selection" = 0.
The maximum value of the setting range differs according to the Pr. 1 "Maximum frequency"
(Parameter 18 "High speed maximum frequency") and it can be calculated from the following
formula:
Note that the maximum setting value of Pr. 37 is 9998 if the result of the above formula exceeds 9998.
To display the machine speed set Pr. 37 to the reference value for the speed to be shown at 60 Hz. For
example, if the speed is 55 m/min at 60 Hz set Pr. 37 to "55". The display will then show "55" when the
motor frequency is 60 Hz.
Purpose
Parameters that must be set
Refer to
Section
Display motor speed
Set speed
Speed display and speed setting
Pr. 37
Change PU monitor display data
DU/PU main display data selection
Cumulative monitor clear
Pr. 52, Pr. 54,
Pr. 170, Pr. 171,
Pr. 268, Pr. 563,
Pr. 564
Change of the monitor output from
terminal AM
Terminal AM function selection
Pr. 158
Set the reference of the monitor
output from terminal AM
Terminal AM standard setting
Pr. 55, Pr. 56
Adjust terminal AM outputs
Terminal AM calibration
Pr. 645, Pr. 900
Pr. No. Name
Initial
Setting
Setting
Range
Description
Parameters referred to
Refer to
Section
37
Speed display
0
0
Frequency display, setting
1
52
800
Maximum
frequency
DU/PU main display
data selection
Control method
selection
0.01–9998
Set the machine speed at 60Hz.
Maximum setting value of Pr. 37
16777.215 60 [Hz]
Setting value of Pr. 1 (Pr. 18) [Hz]
---------------------------------------------------------------------------------------
<
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......