Set V/F pattern
Parameter
6 - 56
6.5 Set
V/F
pattern
6.5.1
Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47)
Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
햲
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Setting of base frequency (Pr. 3)
When operating a standard motor, generally set the rated frequency of the motor to Pr. 3 "Base
frequency".
When running the motor using commercial power supply-inverter switch-over operation, set Pr. 3 to
the same value as the power supply frequency.
If the frequency given on the motor rating plate is "60 Hz" only, always set to "60 Hz". It may result in
an inverter trip due to overload. Caution must be taken especially when Pr. 14 "Load pattern selection"
= "1" (variable torque load)
Purpose
Parameters that must be set
Refer to
Section
Set motor ratings
Base frequency, Base frequency voltage
Pr. 3, Pr. 19,
Pr. 47
Select a V/F pattern according to
applications
Load pattern selection
Pr. 14
Pr. No. Name
Initial Value
Setting Range
Description
Parameters referred to
Refer to
Section
3
Base frequency
50Hz
0–400 Hz
Set the frequency when the motor rated torque
is generated. (50 Hz/60 Hz)
14
29
83
84
178–184
Load pattern selection
Acceleration/
deceleration pattern
selection
Motor rated voltage
Rated motor frequency
Input terminal function
selection
General-purpose
magnetic flux vector
control
Advanced magnetic flux
vector control
19
Base frequency voltage
햲
8888
0–1000 V
Set the rated motor voltage.
8888
95% of power supply voltage
9999
Same as power supply voltage
47
Second V/F
(base frequency)
햲
9999
0–400 Hz
Set the base frequency when the RT signal is on.
9999
Second V/F invalid
I000003aC
Fig. 6-13:
Output voltage related to the output frequency
V/F
V/F
V/F
Base frequency setting range
S
etting r
ange P
r. 19
Output v
oltage r
ela
ted t
o the
po
w
er supply v
oltage
Pr. 3 = 50 Hz, Pr. 19 = 9999
Pr. 3 = 60 Hz, Pr. 19 = 220 V
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......