Basic settings
PU operation mode
FR-E700 SC EC/ENE
5 - 21
5.2.1
Set the set frequency to operate
쑶
Possible faults:
●
Operation cannot be performed at the set frequency.
– Did you press the SET key within 5 s after turning the digital dial?
●
The frequency does not change by turning the digital dial.
– Check to see if the operation mode selected is the external operation mode.
(Press the PU/EXT key to change to the PU operation mode.)
●
Operation does not change to the PU operation mode.
– Check that "0" (initial value) is set in Pr. 79 "Operation mode selection".
– Check that the start command is not on.
Example
쑴
Performing operation at 30 Hz
I001767E
Fig. 5-12:
Frequency setting with the digital dial
햲
Screen at powering on
The monitor display appears.
햳
Press the PU/EXT key to choose the PU
operation mode.
햴
Turn the digital dial to show the
frequency you want to set.
The frequency flickers for about 5 s.
햵
While the value is flickering press the
SET key to set the frequency.
(If you do not press the SET key, the
value flickers for about 5 s and the
display returns to 0.00 (display) Hz.
At this time, return to step
햴
and set
the frequency again.)
햶
After the value flickered for about 3 s,
the display returns to 0.00 (monitor
display). Press the RUN key
to start operation.
햷
To change the set frequency, perform
the operation in above steps
햴
and
햵
.
(Starts from the previously set
frequency.)
햸
Press the STOP/RESET key to stop.
Operation
Display
Flickers for about 5s.
Flicker ... Frequency setting complete!
PU indication is lit.
3s later
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......