Wiring
Control circuit specifications
FR-E700 SC EC/ENE
3 - 27
3.4.4
Changing the control logic
FR-E700SC frequency inverters offer the possibility of choosing between two types of control logic.
Depending on the direction of the flowing current, one distinguishes between:
●
In source logic, a signal switches on when a current flows into the corresponding signal input
terminal. Terminal PC is common to the contact input signals. Terminal SE is common to the open
collector output signals.
●
In sink logic, a signal switches on when a current flows from the corresponding signal input
terminal. Terminal SD is common to the contact input signals. Terminal SE is common to the open
collector output signals.
The input signals are set to source logic (SOURCE) when shipped from the factory. To change the con-
trol logic, the jumper connector above the control circuit terminal block must be moved to the other
position.
(The output signals may be used in either the sink or source logic independently of the jumper con-
nector position.)
I001029E_Logiktausch
Fig. 3-17:
Changing the control logic
Fig. 3-18:
Changing the control logic
I002127E
RUN
RUN
Current flow concerning the input/output
signals when sink logic is selected
Current flow concerning the input/output
signals when source logic is selected
Current
Current
SINK
SOURCE
FR-E700SC
DC input (sink type)
Example: AX40
DC input (source type)
Example: AX80
Current
Current
+
–
+
FR-E700SC
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......