Selection and protection of a motor
Parameter
6 - 98
To enter the Pr. 90 and Pr. 94 motor constants in [mH]
햲
Set Pr. 71 according to the motor used:
햲
For other settings of Pr. 71, refer to section 6.8.2.
햳
In the parameter setting mode, read the following parameters and set desired values.
Calculate the Pr. 94 value from the following formula.
R1: Primary resistance
R2: Secondary resistance
l1:
Primary leakage inductance
l2:
Secondary leakage inductance
M: Excitation inductance
S:
Slip
L1 = l1 + M: Primary inductance
L2 = l2 + M: Secondary inductance
Motor
Pr. 71
햲
Mitsubishi standard motor,
Mitsubishi high efficiency motor
SF-JR
0
SF-HR
40
Mitsubishi constant-torque motor
SF-JRCA 4P
1
SF-HRCA
50
Tab. 6-21:
Motor selection
Fig. 6-40:
Motor equivalent circuit diagram
I001556E
Pr. 94
1
M
2
L1 L2
-------------------
–
100 [%]
=
R1
l1
l2
M
R2/S
U