Parameter
Communication operation and setting
FR-E700 SC EC/ENE
6 - 289
Ethernet IP address for command source selection (Pr. 844 to Pr. 849)
●
To limit the network devices that send the operation or speed command through the Ethernet
network (MODBUS®/TCP or CC-Link IE Field Network Basic), set the range of IP addresses of the
devices.
●
When Pr. 844 to Pr. 847 = "0 (initial value)", no IP address is specified for sending commands
through the Ethernet network. In this case, operation through the Ethernet network (MODBUS®/
TCP or CC-Link IE Field Network Basic) is not available.
●
When four or more clients attempt a connection to the inverter during MODBUS®/TCP communi-
cation, the connection attempted from outside of the IP address range set for Ethernet command
source selection may be forced to be closed.
●
The setting range for command source selection depends on the settings in Pr. 846 and Pr. 848,
and Pr. 847 and Pr. 849.
(Either of the settings can be larger than the other in Pr. 846 and Pr. 848, and Pr. 847 and Pr. 849.)
쑶
쑶
●
When "9999 (initial value)" is set in Pr. 848 and Pr. 849, the range is invalid.
Example
쑴
Setting example 1:
In this case, the IP address range for command source selection via Ethernet communication is
"192.168.x (1 to 3).xxx (100 to 150)".
I003112A
Fig. 6-141:
Setting example 1 for the Ethernet IP address for command source selection
Example
쑴
Setting example 2:
In this case, the IP address range in which Ethernet communication is permitted is
"192.168.2.xxx (50 to 100)".
I003113A
Abb. 6-142:
Einstellbeispiel 2 zum IP-Adressbereich für Betriebsanweisungen
192
168
1
100
ʊ
ʊ
3
150
The range is between
the values set in both
parameters.
The range is between
the values set in both
parameters.
Ethernet IP address for
command source
selection
Command source selec-
tion range setting for the
Ethernet IP address
Pr. 844
Pr. 845
Pr. 846
Pr. 847
Pr. 848
Pr. 849
192
168
2
100
ʊ
ʊ
9999
50
The range is between
the values set in both
parameters.
Ethernet IP address for
command source
selection
Command source selec-
tion range setting for the
Ethernet IP address
Pr. 844
Pr. 845
Pr. 846
Pr. 847
Pr. 848
Pr. 849
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......