Parameter
Selection and protection of a motor
FR-E700 SC EC/ENE
6 - 85
Set two different electronic thermal O/L relays (Pr. 51)
Use this function when running two motors of different rated currents individually by a single invert-
er. (When running two motors together, use external thermal relays.)
Set the rated current of the second motor to Pr. 51. When the RT signal is on, thermal protection is pro-
vided based on the Pr. 51 setting.
For the terminal used for RT signal input, set "3" in any of Pr. 178 to Pr. 184 "Input terminal function se-
lection" to assign the function.
쐌
Output current value is used to perform integration processing.
왕
Output current is assumed as 0 A to perform integration processing. (cooling processing)
—
Electronic thermal relay function is not activated.
Fig. 6-37:
Running two motors by a single inverter
I001137C
Pr. 450
Second Applied
Motor
Pr. 9
Electronic Thermal
O/L Relay
Pr. 51
Second Electronic
Thermal O/L Relay
RT = OFF
RT = ON
1. Motor
2. Motor
1. Motor
2. Motor
9999
0
9999
—
—
—
—
0
—
—
—
—
0.01–500
—
왕
—
쐌
9999
0
9999
쐌
—
쐌
—
0
쐌
—
왕
—
0.01–500
쐌
왕
왕
쐌
9999
0
9999
—
—
—
—
0
—
—
—
—
0.01–500
—
왕
—
쐌
9999
0
9999
쐌
왕
왕
쐌
0
쐌
—
왕
—
0.01–500 (0.1–3600)
쐌
왕
왕
쐌
Tab. 6-8:
Switching the electronic thermal O/L relay
NOTE
The RT signal acts as the second function selection signal and makes the other second functions
valid. (Refer to section 6.10.3.)
M
3~
M
3~
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......