Parameter
Selection of operation mode and operation location
FR-E700 SC EC/ENE
6 - 217
When switching between the network operation mode and external operation mode:
햲
Set Pr. 79 to "0" (initial value), "2", "6" or "7". (At the Pr. 79 setting of "7", the operation mode can
be switched when the X12 (MRS) signal turns on.)
햳
Set "0 (initial value) or 1" in Pr. 340 "Communication startup mode selection".
햴
Set "66" to any of Pr. 178 to Pr. 184 to assign the external-NET operation switching signal (X66) to
the external terminal.
햵
The operation mode changes to network operation mode when the X66 signal turns on, or to
external operation mode when the X66 signal turns off.
햲
PU operation mode also when Pr. 550 "NET mode operation command source selection" = 1
(communication option control source) and the communication option is not fitted.
햳
PU operation mode when the X16 signal is off. When the X65 signal has been assigned, the
operation mode changes with the ON/OFF state of the X65 signal.
Pr. 340
Pr. 79
X66-Signal
Remarks
ON (PU)
OFF (NET)
0
(initial
value)/
1
0 (initial value)
NET operation
mode
햲
External
operation mode
햳
1
PU operation mode
Fixed to PU operation mode
2
NET operation
mode
햲
External
operation mode
Cannot be switched to PU operation mode
3 / 4
External/PU combined operation mode
External/PU combined mode fixed
6
NET operation
mode
햲
External
operation mode
햳
Operation mode can be switched with
operation continued
7
X12 (MRS) ON
NET operation
mode
햲
External
operation mode
햳
Output stop in external operation mode
X12 (MRS) OFF
External operation mode
Forcibly switched to external operation
mode
Tab. 6-59:
Operation mode switching by signal X66
NOTES
The priorities of Pr. 79, Pr. 340 and signals are:
Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340
Changing the terminal assignment using Pr. 178 to Pr. 184 "Input terminal function selection" may
affect the other functions. Please make setting after confirming the function of each terminal.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......