Selection of operation mode and operation location
Parameter
6 - 218
6.18.2
Operation mode at power on (Pr. 79, Pr. 340)
When power is switched on or when power comes back on after instantaneous power failure, the
inverter can be started up in network operation mode.
After the inverter has started up in the network operation mode, parameter write and operation can
be performed from a program.
Set this mode for communication operation using the inverter RS-485 terminals or communication
option.
The above parameters can be changed during a stop in any operation mode.
햲
The above parameter can be set when Pr. 160 "User group read selection" = 0. However, the
parameters can be set whenever the communication option is connected. (Refer to section
6.17.4.)
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
79
Operation mode selection
0
0–4/6/7
Select the operation mode.
(Refer to page 6-209)
79 Operation mode selection 6.18.1
340
Communication start-up
mode selection
햲
0
0
As set in Pr. 79.
1
Started in network operation mode.
10
Started in network operation mode. Operation mode
can be changed between the PU operation mode and
network operation mode from the operation panel.
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......