background image

Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50, 12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, [email protected]

Datasheet 3.50-32.020-01-EN

DS230/4..32 Actuating Drives

Issue 2009-03-15

A

Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications -

 

Reservado el derecho a modificación

 

- Wijzigingen

voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Zm

ě

ny vyhrazeny - Zmiany zastrze

ż

one - 

Возможны

 

изменения

 

-

A változtatások jogát fenntartjuk -

 

保留未经通知而改动的权力

Product Description

DS230/4..32 Actuating Drives

Application

DS230/4, DS230/8, DS230/16, DS230/24 and DS230/32 actuating 
drives with 2-point or 3-point control are used to control air dampers 
in VAC plants.
The drives are equipped with a universal adapter and are mounted 
directly on the air damper axle.

Contents Page

Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3

Technical Data.....................................................................................................................................................3
Accessories (not included in delivery) .................................................................................................................3
Dimensions ..........................................................................................................................................................4
Connection...........................................................................................................................................................4

Installation..............................................................................................................................................................5
Commissioning ......................................................................................................................................................6

Setting rotational direction and rotational angle limitation DS230/4 ....................................................................6
Setting rotational direction DS230/8..32 ..............................................................................................................8
Rotational angle limitation DS230/8..32...............................................................................................................9
DS230/4..32/E auxiliary switch setting...............................................................................................................10

Summary of Contents for DS230

Page 1: ...enntartjuk 保留未经通知而改动的权力 Product Description DS230 4 32 Actuating Drives Application DS230 4 DS230 8 DS230 16 DS230 24 and DS230 32 actuating drives with 2 point or 3 point control are used to control air dampers in VAC plants The drives are equipped with a universal adapter and are mounted directly on the air damper axle Contents Page Important Information Regarding Product Safety 2 Item 3 Technic...

Page 2: ...ator to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training knowledge and experience as well as knowledge of the appropriate regulations Meaning of...

Page 3: ...or damper surface area up to 0 8 m 8 Nm for damper surface area up to 2 m 16 Nm for damper surface area up to 4 m 24 Nm for damper surface area up to 6 m 32 Nm for damper surface area up to 8 m Rotational angle 0 to 90 working range invertible rotational direction DS230 4 Rotational angle limitation 0 to 30 and 60 to 90 pos sible DS230 8 32 Rotational angle limitation 5 to 85 in 5 increments possi...

Page 4: ...l 2 point control Parallel control of up to max 5 DS230 possible Additional connection for auxiliary switches AC 230 V 3 1 5 A contact position at 0 Additional connection for feedback potentiometer 1 2 3 DS230 4 32 230 V AC N L1 1 2 3 DS230 4 32 230 V AC N L1 DS230 4 E 21 22 23 24 25 26 DS230 8 32 E 21 22 23 24 25 11 12 13 0 100 1kΩ DS R1 1000 ...

Page 5: ...ctrical system can cause death due to electric shock Mount or remove only when power is switched off Comply with VDE guidelines and local wiring regulations when mounting removing NOTICE Observe mounting and setting instructions DS230 4 DS230 8 32 ZKGH Accessories Only for DS230 8 32 1 Air damper axle 2 2 pieces KG8 3 Centering pin 4 Actuating lever 1 1 2 3 4 ...

Page 6: ...e death due to electric shock Disconnect the actuating drive from power before removing the cover Fig DS230 4 1 Cover screw 2 Sliding switch for manual adjustment Actual product not shown 3 Clamping screw for securing the air damper axle 4 Left stop for mechanical limitation of rotational angle adjustable 0 to 30 5 Connection terminal 6 Cable bushing 7 Plug 8 Right stop for mechanical limitation o...

Page 7: ... DS230 4 32 Actuating Drives Product Description Note Screws 4 and 8 can be used to reduce the 90 angle working range by 30 each from the two end positions Turn the plug 7 from the motor connection by 180 to reverse the direction of rotation ...

Page 8: ...th due to electric shock Disconnect the actuating drive from power before removing the cover Fig DS24 8 32 1 Cover screw 2 Sliding switch for manual adjustment Actual product not shown 3 Clamping screw for securing the air damper axle 4 Plug 5 Connection terminal 6 Cable bushing 7 Pressure pin for manual adjustment Turn the plug 4 from the motor connection by 180 to reverse the direction of rotati...

Page 9: ...to be limited Setting Example Proceed as follows to limit the rotational range to 0 to 60 from 0 to 90 1 Adapter Set actuating drive to 90 rotational angle for end position Disengage the adapter s retaining clips 1 on the underside of the actuating drive and pull out the adapter 1 to the front of the unit Re insert the adapter 1 in the new end posi tion of 60 rotational angle Push in the adapter 1...

Page 10: ...nal angle Move sliding switch for manual adjustment and set adapter to 70 rotational angle Turn ratchet wheel D2 until microswitch E2 switches Replace the cover switch on mains power supply and perform operational check Actual product not shown 1 Adapter with position indicator 2 Operating pins with the two micro switches 3 Connection terminal for auxiliary switches 4 Pressure pin for manual adjus...

Reviews: