Datasheet 3.50-32.020-01-EN

DS230/4..32 Actuating Drives

Product Description

Item

Technical Data

Accessories (not included in delivery)

DS230/4

AC 230 V actuating drive with 4 Nm torque

DS230/8

As above, but with 8 Nm torque

DS230/16

As above, but with 16 Nm torque

DS230/24

As above, but with 24 Nm torque

DS230/32

As above, but with 32 Nm torque

DS230/../E

Data same as for DS230/4..32, but with 2 adjustable auxiliary switches

DS230/../R1/1000

Data same as for DS230/4..32, but with feedback potentiometer 1 k

Ω

Nominal voltage

AC 230 V

Power consumption

In operation
In end position

DS230/4 4.0 W; DS230/8..24 5.0 W; DS230/32 5.5 W
DS230/4 3.0 W; DS230/8..24 0.5 W; DS230/32 1.0 W

Control

2-point or 3-point signal AC 24 V (open/close or open/stop/close)

Position indication

Scale on actuating drive 
and DS230/../R1/1000 over feedback potentiometer 1 k

Ω

Torque

DS230/4
DS230/8
DS230/16
DS230/24
DS230/32

 4 Nm for damper surface area up to 0.8 m²
 8 Nm for damper surface area up to 2 m²
16 Nm for damper surface area up to 4 m²
24 Nm for damper surface area up to 6 m²
32 Nm for damper surface area up to 8 m²

Rotational angle

0 to 90° working range, invertible rotational direction
DS230/4

Rotational angle limitation: 0 to 30° and 60° to 90° pos-
sible

DS230/8..32

Rotational angle limitation: 5° to 85° in 5° increments 
possible

Run time

DS230/4
DS230/8
DS230/16
DS230/24
DS230/32

35 s for 90° rotational angle
30 s for 90° rotational angle
80 s for 90° rotational angle
125 s for 90° rotational angle
140 s for 90° rotational angle

Auxiliary switches

DS230/../E  2 adjustable auxiliary switches, AC 230 V, 3 (1.5) A, deliv-
ery setting: 10° and 80° rotational angle

Potentiometer

DS230/../R1/1000  feedback potentiometer 1 k

Ω

; 0.5 W, ±10%

Degree of protection

DS230/4
DS230/8..32

IP42 (IP44 with M16 x 1.5 screw fitting) 
IP54 (cable at the bottom)

Ambient temperature

-20 °C to +50 °C 

Ambient humidity

5 to 90% r.h., non-condensing

Weight

DS230/4  0.95 kg; DS230/8..32  1.2 kg

ZKGH

Only for DS230/8..32: one actuating lever with centering pin and two KG8 ball joints

Summary of Contents for DS230

Page 1: ...enntartjuk 保留未经通知而改动的权力 Product Description DS230 4 32 Actuating Drives Application DS230 4 DS230 8 DS230 16 DS230 24 and DS230 32 actuating drives with 2 point or 3 point control are used to control air dampers in VAC plants The drives are equipped with a universal adapter and are mounted directly on the air damper axle Contents Page Important Information Regarding Product Safety 2 Item 3 Technic...

Page 2: ...ator to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training knowledge and experience as well as knowledge of the appropriate regulations Meaning of...

Page 3: ...or damper surface area up to 0 8 m 8 Nm for damper surface area up to 2 m 16 Nm for damper surface area up to 4 m 24 Nm for damper surface area up to 6 m 32 Nm for damper surface area up to 8 m Rotational angle 0 to 90 working range invertible rotational direction DS230 4 Rotational angle limitation 0 to 30 and 60 to 90 pos sible DS230 8 32 Rotational angle limitation 5 to 85 in 5 increments possi...

Page 4: ...l 2 point control Parallel control of up to max 5 DS230 possible Additional connection for auxiliary switches AC 230 V 3 1 5 A contact position at 0 Additional connection for feedback potentiometer 1 2 3 DS230 4 32 230 V AC N L1 1 2 3 DS230 4 32 230 V AC N L1 DS230 4 E 21 22 23 24 25 26 DS230 8 32 E 21 22 23 24 25 11 12 13 0 100 1kΩ DS R1 1000 ...

Page 5: ...ctrical system can cause death due to electric shock Mount or remove only when power is switched off Comply with VDE guidelines and local wiring regulations when mounting removing NOTICE Observe mounting and setting instructions DS230 4 DS230 8 32 ZKGH Accessories Only for DS230 8 32 1 Air damper axle 2 2 pieces KG8 3 Centering pin 4 Actuating lever 1 1 2 3 4 ...

Page 6: ...e death due to electric shock Disconnect the actuating drive from power before removing the cover Fig DS230 4 1 Cover screw 2 Sliding switch for manual adjustment Actual product not shown 3 Clamping screw for securing the air damper axle 4 Left stop for mechanical limitation of rotational angle adjustable 0 to 30 5 Connection terminal 6 Cable bushing 7 Plug 8 Right stop for mechanical limitation o...

Page 7: ... DS230 4 32 Actuating Drives Product Description Note Screws 4 and 8 can be used to reduce the 90 angle working range by 30 each from the two end positions Turn the plug 7 from the motor connection by 180 to reverse the direction of rotation ...

Page 8: ...th due to electric shock Disconnect the actuating drive from power before removing the cover Fig DS24 8 32 1 Cover screw 2 Sliding switch for manual adjustment Actual product not shown 3 Clamping screw for securing the air damper axle 4 Plug 5 Connection terminal 6 Cable bushing 7 Pressure pin for manual adjustment Turn the plug 4 from the motor connection by 180 to reverse the direction of rotati...

Page 9: ...to be limited Setting Example Proceed as follows to limit the rotational range to 0 to 60 from 0 to 90 1 Adapter Set actuating drive to 90 rotational angle for end position Disengage the adapter s retaining clips 1 on the underside of the actuating drive and pull out the adapter 1 to the front of the unit Re insert the adapter 1 in the new end posi tion of 60 rotational angle Push in the adapter 1...

Page 10: ...nal angle Move sliding switch for manual adjustment and set adapter to 70 rotational angle Turn ratchet wheel D2 until microswitch E2 switches Replace the cover switch on mains power supply and perform operational check Actual product not shown 1 Adapter with position indicator 2 Operating pins with the two micro switches 3 Connection terminal for auxiliary switches 4 Pressure pin for manual adjus...

Reviews: