6.6.3
Remote setting function (Pr. 59)
Even if the operation panel is located away from the enclosure, you can use contact signals to perform
continuous variable-speed operation, without using analog signals.
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Pr. 59 can be used to select a digital motor potentiometer. Setting Pr. 59 to a value of "1" activates the
frequency setting storage function, so that the stored value is also stored when the power is switched
off. The last frequency value is stored in the E²PROM. The delete instruction only applies to the data
stored in RAM.
When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL
signals are changed: RH
acceleration, RM
deceleration and RL
clear.
* External operation frequency (other than multi-speed) or PU running frequency.
Pr. No. Name
Initial Value
Setting
Range
Description
Parameters referred to
Refer to
Section
RH, RM and RL
Signal Function
Frequency Setting
Storage Function
59
Remote function
selection
0
0
Multi-speed setting
—
1
18
7
8
44
45
178–184
Maximum frequency
High speed maximum
frequency
Acceleration time
Deceleration time
Second acceleration/
deceleration time
Second deceleration
time
Input terminal
function selection
1
Remote setting
✔
2
Remote setting
—
3
Remote setting
—
(Turning STF/STR off clears
remote setting frequency.)
Fig. 6-25:
Connection diagram for remote setting
I001132E
I001133E
Fig. 6-26:
Example of the remote setting function
Forward rotation
Acceleration
Deceleration
Clear
Inverter
Acceleration RH
Deceleration RM
Clear RL
Forward rotation STF
Power supply
Pr. 59 = 1
Pr. 59 = 2, 3
Pr. 59 = 1, 2
Pr. 59 = 3
Output
fr
equenc
y [H
z]
Time
ON
ON
ON
ON
EIN
ON
ON
ON
ON
ON
ON
Summary of Contents for fr-e700 series
Page 2: ......
Page 4: ......
Page 20: ...Contents XVI ...
Page 112: ...Operation panel Operation 4 20 ...
Page 154: ...External operation Basic settings 5 42 ...
Page 528: ...CC Link IE Field Network Basic Parameter 6 374 ...
Page 562: ...Meters and measuring methods Troubleshooting 7 34 ...
Page 606: ...A 30 Index Appendix ...
Page 607: ......