D5048 

- SIL 3 Digital Output Driver, NE Loads, Loop Powered

 

G.M. International ISM0119-10 

SIL 3 Digital Output Driver, NE Loads, 

Loop Powered, DIN-Rail and 

Termination Board, Model D5048S 

 

D5048S 

INSTRUCTION & SAFETY MANUAL 

Summary of Contents for D5048S

Page 1: ... SIL 3 Digital Output Driver NE Loads Loop Powered G M International ISM0119 10 SIL 3 Digital Output Driver NE Loads Loop Powered DIN Rail and Termination Board Model D5048S D5048S INSTRUCTION SAFETY MANUAL ...

Page 2: ...g open circuit or short circuit detection dip switch selectable When fault is detected output is de energized until normal condition is restored Short output detection load resistance 50 Ω 2 mA forcing to detect fault Open output detection load resistance 10 KΩ Fault signaling voltage free NE SPST optocoupled open collector transistor output de energized in fault condition and when input power not...

Page 3: ...MC INMETRO EAC EX UKR TR n 898 NEPSI TIIS TÜV Certifications TÜV Functional Safety Certification Type Approval Certificate DNV and KR for maritime applications Simplified installation using standard DIN Rail and plug in terminal blocks with or without Power Bus or customized Termination Boards 250 Vrms Um max voltage allowed to the instruments associated with the barrier Model D5048S Output A for ...

Page 4: ...ndicated in the table below Out A 7 10 Out B Out C 8 10 9 10 Io Isc 147 mA Out A Out B 7 10 8 10 Ii Imax D5048 Terminals Out A 7 10 D5048 Associated Apparatus Parameters Cenelec US IIC A B Co Ca 113 nF Co Ca 860 nF Co Ca 3 05 µF IIB C IIA D I Co Ca 4 35 µF Co Ca 860 nF Out C 9 10 Ci Ci device C cable IIC A B Co Ca 113 nF Co Ca 860 nF Co Ca 3 05 µF IIB C IIA D IIC A B Co Ca 113 nF Co Ca 860 nF Co C...

Page 5: ...e cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo If the cable parameters are unknown the following value may be used Capacitance 180pF per meter 60pF per foot Inductance 0 60µH per meter 0 20µH per foot Out A 7 10 IIC A B Lo Ro 39 2 µH Ω Lo Ro 156 8 µH Ω Lo Ro 313 6 µH Ω IIB C IIA D I Lo Ro 514 6 µH Ω Lo Ro 156 8 µH Ω Out C 9 10 Li Ri device and L cable R cable IIC A B L...

Page 6: ...module is directly supplied by the digital output of a Safety PLC if the safety PLC imposes a shutdown state of this module there is no additional power supply which can keep the D5048S output energized in case of an internal fault Therefore all internal faults have either no effect on the safety function or lead to the safe state according to the Safety Function definitions Failure rate data take...

Page 7: ... device to a different terminal block Presence of output as well as integrity or fault condition of device and connecting line are displayed by signaling LEDs yellow for status red for fault Start up Before powering the unit check that all wires are properly connected and verify their polarity also check that Intrinsically Safe conductors and cable trays are segregated no direct contacts with othe...

Page 8: ... dip switch configuration 1 2 3 4 ON Not used SW2 dip switch configuration SW2 Override control input Disabled Enabled 4 4 ON OFF 1 2 3 4 ON Not used Input impedance Iin 10 mA during fault Rin 2 kΩ ON OFF 1 1 SW1 factory settings All DIP switches are ON SW1 Field line and load fault detection 1 OFF 1 ON Disabled Enabled Used for SIL applications Used for SIL applications 1 2 3 4 ON SW2 factory set...